Session: 02-03 Data Center Cooling I
Paper Number: 92005
92005 - Predictions of Airside Economization-Based Air-Cooled Data Center Environmental Burden Reduction
Modern data centers, which consume nearly 3% of global electricity, continue to experience increased demand. Therefore, green data centers that consume less energy and have minimal environmental impact are desirable. This study examines the potential energy savings and environmental benefits of applying airside economization with evaporative cooling in air-cooled data centers in the U.S. A generic data center that employs a Computer Room Air Conditioning (CRAC)-based cooling system with a total IT load of 400 kW is modeled at 925 locations using the National Renewable Energy Laboratory’s (NREL’s) TMY3 database. The energy savings and environmental benefits are evaluated in terms of key data center performance metrics: Power Usage Effectiveness (PUE), Carbon Usage Effectiveness (CUE), and a recently proposed metric Water Scarcity Usage Effectiveness (WSUE), which quantifies the holistic impact of water consumption on regional water availability. Results are aggregated and analyzed at the U.S. State level. It is found that 6.57% and 21.5% of the year in average are feasible for airside economization implementation in the U.S. as per ASHRAE recommended and allowable envelopes, respectively. Specifically, evaporative cooling solution is allowed during 36.7% of the year in CA, which leads to a decrease in these metrics by 16.4% to 16.7%.
Presenting Author: Li Chen Villanova University
Predictions of Airside Economization-Based Air-Cooled Data Center Environmental Burden Reduction